Acti 9 C60NA-DC, SW60-DC, C120NA-DC

Switch-disconnectors for solar generation.

Dedicated to perform safety isolation downstream the photvoltaic cells or upstream the inverter, prior to maintenance.

Acti 9 C60NA-DC, SW60-DC, C120NA-DC
  • Features

    Dedicated to solar generation
    • Compliant with IEC 60947-3, suitable for isolation, with padlocking feature
    • Maximum operating voltage : 1000 V DC
    • compatible with auxiliaries for remote position indication, or intentional tripping

    Acti 9 SW60-DC :

      • disconnection upstream the inverter, prior to maintenance operation.
      • rated current : 50 A
      • polarity sensitive

    Acti 9 C60NA-DC

      • disconnection of strings downstream the photvoltaic panels or upstream the inverter, prior to maintenance operation.
      • max rated current : 50 A under 700 V, 32 A under 800 V, 20 A under 1000 V

    Acti 9 C120NA-DC

      • disconnection of strings downstream the photvoltaic panels or upstream the inverter, prior to maintenance operation.
      • max rated current : 100 A (under 1000 V)


     The selection of Acti 9 C60NA-DC, Acti 9 C120NA-DC or Acti 9 SW60-DC depends on the installation requirements:

                                                    Operating Voltage (Ue)   - Polarized
    Acti 9 C60NA-DC 20A:                 1000 VDC                         No
    Acti 9 C60NA-DC 32A:                   800 VDC                         No
    Acti 9 C60NA-DC 50A:                   700 VDC                         No
    Acti 9 C120NA-DC 100A:             1000 VDC                         No
    Acti 9 SW60-DC 50A:                    1000 VDC                        Yes

    Whereas Acti 9 C60NA-DC and Acti 9 C120NA-DC are non-polarized, Acti 9 SW60-DC is sensitive and (+) and (-) need to be respected for connection.