output interface module - 17.5 mm - electromechanical - 24 V AC/DC - 1 NC + 1 NO
Show more characteristics >-
Characteristics
Main range of product Interface for discrete signalsproduct or component type Electromechanical output interface modulecontacts type and composition 1 NC + 1 NO[Uc] control circuit voltage 24 Vcontrol circuit type AC/DCcontrol circuit frequency 50/60 Hzwidth pitch dimension 17.5 mm[In] rated current <= 55 mA AC<= 62 mA DCshort-circuit protection 16 A external fuse gF (Ik <= 2.5 kA AC and Ik <= 100 A DC)16 A external fuse gG (Ik <= 2.5 kA AC and Ik <= 100 A DC)[Ith] conventional free air thermal current 12 A conforming to IEC 60947-1local signalling Green mechanical indicator for position of contacts and 1 green LED control signal stateComplementary control circuit voltage limits 30 V energization threshold: 16.5 Vmaximum switching voltage 125 V DChousing colour Greyconnections - terminals Screw clamp terminaldrop-out voltage 3.8 Vholding current >= 4.9 mA DC>= 5.2 mA ACpower dissipation in W <= 1.5 W[Ue] rated operational voltage <= 125 V DC conforming to IEC 60947-5-1<= 230 V AC conforming to IEC 60947-5-1network frequency 50/60 Hz[Ie] rated operational current 1 A AC-13 Ue: 230 V per 1000000 cycles conforming to IEC 60947-5-11 A AC-14 Ue: 230 V per 1000000 cycles conforming to IEC 60947-5-11 A AC-15 Ue: 230 V per 1000000 cycles conforming to IEC 60947-5-11 A DC-13 Ue: 24 V per 1000000 cycles conforming to IEC 60947-5-14 A AC-12 Ue: 230 V per 1000000 cycles conforming to IEC 60947-5-15 A DC-12 Ue: 24 V per 1000000 cycles conforming to IEC 60947-5-1minimum switching current 3 mAminimum switching voltage 17 Velectrical reliability <= 0.00000001operating time <= 12 ms between de-energisation of coil and closing of NC contact<= 12 ms between de-energisation of coil and closing of NO contact<= 12 ms between energisation of coil and closing of NC contact<= 12 ms between energisation of coil and closing of NO contactcontact bounce time <= 3 msoverlap time 1 msoperating rate in Hz 6 Hz at no-load0.5 Hz at Iemechanical durability 10000000 cycles[Ui] rated insulation voltage 250 V conforming to IEC 60947-1250 V conforming to VDE 0110 group Cflame retardance V0 conforming to UL 94cable cross section 0.27...4 mm², 1 wire rigid0.34...2.5 mm², 1 or 2 wires flexible with cable end0.6...2.5 mm², 1 or 2 wires flexible without cable end0.27...2.5 mm², 2 wires rigidoperating position Any positioninstallation category II conforming to IEC 60947-1mounting support Asymmetrical DIN railCombination railSymmetrical DIN railproduct weight 0.095 kgEnvironment immunity to microbreaks 8 msdielectric strength 1500 V for 1 minute between independent contacts2500 V for 1 minute between wired interface and earth4000 V for 1 minute between coil circuit and contact circuitsstandards IEC 60947-5-1product certifications BVCSADNVLROS (Lloyds register of shipping)ULIP degree of protection IP20 conforming to IEC 60529protective treatment TCfire resistance 850 °C conforming to IEC 60695-2-1shock resistance 50 gn for 11 ms conforming to IEC 60068-2-27vibration resistance 6 gn (f = 10...55 Hz) conforming to IEC 60068-2-6electromagnetic compatibility 1.2/50 ms shock waves immunity test, 0.25 kV for U > 50 V conforming to IEC 255-41.2/50 ms shock waves immunity test, 0.5 kV for U < 50 V conforming to IEC 255-4Electrostatic discharge immunity test level 3, 8 kV conforming to IEC 61000-4-2Rapid transients immunity test, on input/output 1 kV conforming to IEC 61000-4-4Rapid transients immunity test, on power supply 2 kV conforming to IEC 61000-4-4ambient air temperature for operation -20...60 °C at Un-5...40 °C unrestricted operationambient air temperature for storage -40...70 °Coperating altitude <= 3000 mpollution degree 3 conforming to IEC 60947-5-1Contractual warranty Warranty period 18 months -
Documents & Downloads
Language- English
- Spanish
- Portuguese
- French
- Italian
- German
CertificateSizeAdd to My DocumentsCSA Certificate ABR-1 ABR-2 ABS-2 (Version 1.0)Instruction sheetSizeAdd to My DocumentsABR1E.../1S... Electromechanical interface modules (Version 07)Declaration of conformitySizeAdd to My DocumentsEU DOC - Zelio Interfaces ABR-1 ABR-2 ABS-2 (Version 1.0)Marine certificateSizeAdd to My DocumentsDNV-GL Marine Certificate ABR-1 ABR-2 ABS-2 interface modules (Version 1.0)Product Environmental ProfileSizeAdd to My DocumentsABR... Electromechanical Interface Modules, Product Environmental Profile (Version 1.0)Date 6/23/17Size 3.4 MB -
Technical FAQs
No results found.Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later. -
Dimensions Drawings
Electromechanical Interface ModuleDimensions -
Connections and Schema
Electromechanical Interface ModuleExample of Application with PLCInterfacing PLC discrete outputs
(1)Essential on inductive loads (can be replaced with peak limiter)(2)PLC positive logic transistor (or relay) outputsInterface with Mechanical Indication + LEDCircuit Diagram1 N/C + 1 N/O
-
Performance Curves
Electrical Durability of ContactsAC LoadsTest conditions: in accordance with standard IEC 947-5-1 set up for rated control voltage, operating rate: 1800 cycles/hour. (0.5 Hz).
AC-12 operating cycles in millions
AC-12Control of resistive loads and isolated solid state loads via optocoupler (cos ϕ ≥ 0.9)(1)24 V(2)48 V(3)127 V(4)230 VAC-13 operating cycles in millions
AC-13Control of isolated solid state loads via transformer (cos ϕ ≥ 0.65)(1)24 V(2)48 V(3)127 V(4)230 VAC-14 and AC-15 operating cycles in millions
AC-14Control of weak electromagnetic loads of electromagnets ≤ 72 VA (make: cos ϕ = 0.3, break: cos ϕ = 0.3)AC-15Control of electromagnetic loads of electromagnets > 72 VA (make: cos ϕ = 0.7, break: cos ϕ =0.4)(1)24 V(2)48 V(3)127 V(4)230 VDC LoadsTest conditions: in accordance with standard IEC 947-5-1 set up for rated control voltage, operating rate: 1800 cycles/hour. (0.5 Hz).
DC-12 operating cycles in millions
DC-12Control of resistive loads and isolated solid state loads via optocoupler (L/R ≤ 1 ms)(1)24 V(2)48 V(3)127 VDC-13 operating cycles in millions
DC-13Control of electromagnets (L/R ≤ 2 x (Ue x Ie) in ms, with Ue: rated operating voltage and Ie: rated operating current)(1)24 V(2)48 V(3)127 V